Protocol/compatibility |
Compatible with C-TEC’s XFP/ZFP XP95/Discovery Addressable Fire Panels. |
Application/operation |
Designed to be wall mounted. Suitable for use in external areas where IP55 rated devices are deemed sufficient. |
VAD category & coverage |
W-2.4-8.2. |
Flash rate & colour |
0.5Hz / White. |
Supply/operating voltage |
17 to 28V DC (Sounder); 21 to 28V DC (Sounder/VAD). |
Quiescent current |
550µA @ 24 VDC. |
Nominal SPL (Sound Pressure Level) |
103dB(A) when set to tone 1. |
Alarm current |
14mA (VAD lit, Sounder on max). |
Indicators |
Polling (green LED) & Short Circuit Isolator Active (amber LED). |
Product dimensions (mm) |
114mm diameter x 131mm deep. |
IP Rating |
IP55. |
Weight |
315g. |
Operating conditions/temperature |
-10ºC to +55ºC. Max. 95% RH (Non-condensing). |
Notes |
Includes the same lens and electronics as our EN54-23, 3 & 17 certified Hi-Output Sounder VAD but is IP55 rated. |