Approvals/certifications |
Certified to EN54-7 by Intertek (0359-CPR-00183). |
Application/operation |
Uses an IR light source & photodiode to detect smoke. Typically used in escape routes, living areas, bedrooms & other enclosed spaces. Particularly effective at detecting slow burning fires caused by overheated electrical wiring or smouldering materials. |
Application temperature |
n/a. |
Static response temperature |
n/a. |
Sensitivity |
Nominal alarm threshold of 0.16db/m obscuration measured in accordance with EN54-7:2000. |
Supply wiring |
2-wire monitored, polarity sensitive. |
Supply/operating voltage |
9 to 33V DC. |
Quiescent current |
30µA @ 24 VDC. |
Alarm voltage |
6-33V DC. |
Alarm current |
19mA @ 12-33V DC; 11mA @ 9V DC; 2.5mA@ 6V DC. |
Alarm reset voltage |
Less than 1V DC (+0.5 seconds alarm reset time). |
Expansion connections |
Remote LED output available via ActiV base. Current source to the negative line, short-circuit protected. Max voltage 2.7V DC. |
Product dimensions (mm) |
102.2mm diameter x 37mm deep (detector in base); 102.2mm diameter x 57.5mm deep. |
Construction & finish |
White polycarbonate casing rated to UL94 V-2 with nylon parts. |
IP Rating |
IP42. |
Weight |
99g. |
Reviews