Protocol/compatibility |
Compatible with C-TEC’s XFP/ZFP XP95/Discovery Addressable Fire Panels. To communicate with the host fire panel, the XFP508X requires 2 addresses, one so it can be recognised as a Zone Monitor, another as a Sounder Control Unit. |
Power requirements |
22-40V DC (derived from the host panel’s Apollo XP95/Discovery addressable loop). |
Quiescent current |
5mA. |
No. of detector zone circuits |
1. |
Max. detector circuit length |
100m. |
Call point resistor value |
Manual call points must be fitted with a 330Ω resistor in order to immediately trigger the host panel on operation. Note one 330Ω resistor is supplied in the Hush Button’s accessory pack. |
Max. devices per detector zone |
10 (any mix of detectors and manual call points). |
No. of conventional sounder circuits |
1. |
Max. sounder circuit length |
100m. |
EOL resistor value |
6800Ω 5% Tol. 0/25W (blue, grey, red, gold). |
Alarm current |
30mA, 20mA or 12.5mA (selectable via PLK2 output selector link). |
Max. sounder output current |
30mA. |
Indicators |
‘Supply present’ LED; ‘Local alarm’ LED; ‘Hushed’ LED (Lit steady when in the Hushed state, flashes during the last 15 seconds of any Hushed period); ‘Fault’ LED. Also includes a beeper that sounds during the last 15 seconds of any Hushed period. |
Product dimensions (mm) |
146 W x 86 H x 26 D mm (Can be mounted on a standard UK 25mm double gang flush or surface back box). |
Construction & finish |
Supplied in brushed stainless steel. |
IP Rating |
IP41. |
Weight |
226g. |
Operating conditions/temperature |
-5ºC to +40ºC. Max relative humidity: 95%. |