Nec adipiscing luctus consequat penatibus parturient massa cubilia etiam.

SAP 1 Loop 16 Zone Addressable Sprinkler Monitoring Panel (XP95/Discovery protocol)

£357.71

  • Ideal for monitoring up to 126 sprinkler flow switches.
  • One switch monitoring unit required per monitored flow switch.
  • Utilises the same technology as C-TEC’s popular XFP addressable fire panel.
  • Up to 16 sprinkler zone indicators available (assignable via the panel’s PC programming tools).
  • Attractive flush or surface mountable plastic enclosure.
  • Combined keypad or keyswitch entry.
SKU: SAP501E/X Category: Tags: , ,

Description

Protocol/compatibility Apollo XP95/Discovery.
Mains supply 230V 50/60Hz.
Mains rated current 350mA maximum.
Internal power supply 27Vdc nominal.
Total output current limited to 1.4A @ 230Vac (Imax.A 210mA; Imin. 40mA).
Quiescent current 50mA (loop unloaded).
Max battery size and type 2 x 12V 3.2Ah VRLA connected in series.
No. of loop drivers 1.
Max. loop output current 500mA (25V min; 34V max).
Max. loop length 1KM.
Max. addressable devices per loop 126.
No. of conventional sounder circuits 2 (Max. length per circuit is 500m).
EOL resistor value 6800Ω 5% Tol. 0/25W (blue, grey, red, gold).
Max. sounder output current 400mA.
Auxiliary relays 3 x Programmable Relays (programmable from C&Es). 1 x Fault Relay (active when no faults are present). Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc.
Other outputs 24V Aux. Power (19.5V min, 28V max). Protected by a resettable fuse. Max. current 100mA.
Auxiliary inputs 2 x Programmable Inputs (programmable from C&Es). Connect to 0V to trigger, Max. input voltage 27V (non-latching).
PC connection PC connection via RS232 molex connector (supplied in XFP507 upload/download software kit); No printer connection available.
Indicators 2 line x 40 character backlit display; 16 Zonal LEDs, General Fire; Energised; Pre-Alarm; Remote Output Activated; Remote Output Disabled; Accessed; Disablement; Test; Silenced; General Fault; System Fault.
Connections Fixed, largest acceptable conductor size 1mm2.
Expansion connections 2-wire RS485 non-redundant network/repeater connection available via optional XFP761 network card. Max. 8 mains per network or 8 repeaters per non-networked main. Limit 1KM (main panel network) or 500M (repeater network).
Product dimensions (mm) 380 W x 235 H x D 96mm;
Construction & finish Plastic lid and base; RAL7035 textured.
IP Rating IP30.
Weight 1.8kg (without batteries).
Operating conditions/temperature -5ºC to +40ºC. Max relative humidity: 95%.